Testimonials

Joe Barrat | 5 out of 5 Stars!
"Just wanted to thank you for your prompt and efficient service calibrating my PAT tester. The whole process was effortless. Just what we like! Many thanks".

Cliff Jones | 5 out of 5 Stars!
"We required a pat test calibration on one of our machines, from start to finish we was notified and was updated on our order. The order was dealt with very professionally and would highly recommend PTS Calibrations and Gary for a job well done many thanks 10 stars **********". 
Stephan | 5 out of 5 Stars!
"Quick and professional turnaround.
Need our meter calibration unit calibrated due to NSI visits and engineer site visits. PTS kindly calibrated unit in a timely manner and delivered back to our office."

Adrian Carrotte | 5 out of 5 Stars!
"We have used them twice and i can say that we will continue to use them as long as we can.
Fast turn around and send back. If I could give them 10 out of 10 I would.
Very helpful people"

Contact Form

Calibration Booking

*
*
*
*
*

Basic PAT Testers

Entry level PAT Testers
Sort By:  
Seaward Primetest 100
Seaward Primetest 100 (PT100)

The large LCD display shows the test results values as well as a PASS or FAIL indication. This piece of portable appliance testing equipment is battery powered and lightweight to enable quick and efficient portable appliance testing. Please note the PrimeTest 100 does not have a backlight.The PrimeTest 100 is a functional and diverse manual PAT tester. Featuring three operational modes, it is an ideal choice for those looking for an easy to use, electrical safety tester. Simply pushing a button will give you the option of PAT Test mode: Class I and II, IEC Lead test mode or Power Socket mode.

PrimeTest 100 is the fastest, most compact PAT Tester available, providing accurate measurements of Earth Bond, Insulation, Leakage and mains outlet condition.

The simple 3 button operation facilitates quick and accurate PAT testing at the touch of the button.

The PrimeTest 100 portable appliance tester is ideal for all application where comprehensive and regular testing as required.

The unique design of the PrimeTest 100 incorporates Seaward’s High/Low current test techniques which ensure accurate and repeatable measurement where other testers struggle to provide reliable readings.

An inbuilt socket tester allows the user to ensure that the mains supply has been correctly wired.

The PrimeTest 100 is used by 1,000's of people to test millions of appliances every day.


Seaward PrimeTest 100 Technical Specifications

TESTS
Earth Continuity 
Test Current±200mA DC
Display Range0.00 to 19.99Ω
Pass Value0.2Ω
Insulation Range 
Test Voltages500V DC
Display Range0.2 to 19.99MΩ
Pass Value2MΩ
IEC Lead Test 
Tests PerformedEarth Continuity
Insulation Resistance
Live, Neutral Continuity and Polarity
Equivalent Leakage Class I 
Test Voltage40V, 50Hz AC Nominal
Display Range0.10mA to 19.99mA
Pass Value0.75mA
 Equivalent Leakage Class II 
 
Test Voltage40V, 50Hz AC Nominal
Display Range0.10mA to 19.99mA
Pass Value0.25mA
CIRCUIT TESTS 
Power Socket Test 
Input Voltage Range230V + 10% - 15% AC
IndicatorsPhase to Earth Voltage
Phase to Neutral Voltage
Neutral Earth
Additional Information 
Weight and Dimensions 800g/26cm (I) x 10cm (w) x 5.5cm (d)  
Power Source6 x AA batteries
£299.00
Martindale HPAT 500
Martindale HPAT 500 (HPAT500)

The HPAT500 is an easy to use battery powered, hand held PAT tester with simple one-button test selection. It’s lightweight portable design make it ideal for testing in all locations whether under a desk or testing a wall mounted monitor. The tester comes with rechargeable batteries and mains charger for low cost of ownership and can even be used whilst recharging ensuring no downtime.

Simple one button testing
Pass/Fail indicator with test results
Class I, Class II & Lead Test
200mA Earth Bond - IT Safe
500V Insulation Test
Rechargeable batteries

Earth Bond Test (IT Safe)

  • Test Current: 200mA DC
  • Test Voltage: 4V DC
  • Default Pass Value: 0.1Ω
  • Secondary Pass Value: 0.2Ω

Insulation Resistance

  • Test Voltage: >500V DC at 1mA
  • Display Range: 0.20Megohm - 19.99Megohm
  • Pass Value: 1Megohm Class I, 2Megohm Class II

IEC & Extension Lead Test

  • Earth Continuity: 200mA DC
  • Insulation Test: 500V DC
  • Wiring Test: Live, Neutral Continuity& Polarity

Fuse Test

  • Test Voltage: 4V DC
  • Test Current: 200mA DC
  • Pass Level: >2mA

£329.00
Martindale HPAT 500
Martindale HPAT 600 (HPAT600)

The HPAT600 is an easy to use battery powered, hand held PAT tester that is ideal for testing all types of portable appliances. The tester is supplied with rechargeable batteries for low running costs and a mains and in-car charger for convenience. Whilst recharging, the HPAT can still be operated from the mains supply ensuring maximum productivity at all times.
It has a fast automatic one button test sequence or a simple to operate manual mode useful for diagnostics and can be used for testing both 240V and 110V appliances with the optional TL157 adaptor lead

PAT Tester with User Adjustable Pass Limits and Memory
Simple one button testing
Pass/Fail indicator with test results
Class I, Class II & Lead Test
200mA Earth Bond - IT Safe
500V Insulation Test
Rechargeable batteries

Earth Bond Test (IT Safe)

  • Test Current: 200mA DC
  • Test Voltage: 4V DC
  • Range: 0 - 19.99Ω
  • Resolution: 0.01Ω
  • Default Pass Value: 0.1Ω
  • User Selectable Pass Value: 0.1Ω to 0.9Ω in 0.1Ω steps

Insulation Resistance

  • Test Voltage: 
    500V: >500V DC at 1mA 
    250V: >250V DC at 1mA
  • Default Pass Value: Class I - 1MΩ, Class II - 2MΩ
  • User Selectable Pass Value: 0.3MΩ to 1MΩ in 0.1Ω steps, or 1MΩ to 10MΩ in 1MΩ steps

IEC & Extension Lead Test

  • Earth Continuity: 200mA DC
  • Insulation Test: 500V DC
  • Wiring Test: Live, Neutral Continuity& Polarity
  • Earth Bond Default Pass Value: 0.1Ω
  • Earth Bond User Selectable Pass Value: 0.1Ω to 0.9Ω in 0.1Ω steps
  • Insulation Resistance Default Pass Value: 1MΩ
  • Insulation Resistance User Selectable Pass Value: 0.3MΩ to 1MΩ in 0.1Ω steps, or 1MΩ to 10MΩ in 1MΩ steps

Fuse Test

  • Test Voltage: 4V DC
  • Test Current: 200mA DC
  • Pass Level: >2mA

 

£349.00
Kewtech KT71
Kewtech KT71 (KT71)
Amongst the most popular Pat testers on the market The fast automatic test sequences mean that you only turn the knob to the type of test that you want then press start The IET Code of prectise says that if you cannot undertake an insulation test at 500V then you can either conduct a run leakage / touch lekage or 250V insulation - the KT71 enbale you to do these alternative tests in the most simplistic of ways. The KT71 has a lid and test lead pouch to keep everything safe and protected when not in use KEY FEATURES Performs Earth bond at 200mA for IT appliances and high current 20A for all other appliances 250V / 500V insulation test voltages Run / leakage at 230V Single rotary dial position initiates test sequence Class I IT 200mA Earth Bond Class I 20A Earth Bond Class II Memory for test lead resistance compensation Extension lead test – including polarity LED indication of pass / fail as well as a result display Automatic check if appliance is switched on or not Tests 110V appliances for earth bond and insulation (with appropriate test adaptor) Tests in accordance with the IET Code of Practice INCLUDED Mains Leads ACC7209 KAMP-S Short IEC lead for extension lead testing Earth Lead ACC7208 ACC7163 Blade prod Instruction Manual Calibration Certificate WEIGHTS & DIMENSIONS Boxed Weight: 2.1kg Boxed Dimensions: 215(W)x283(H)x93(D)mm
£540.00
Martindale EPAT 1600
Martindale Easypat 1600 (MPAT1600)
The EPAT1600 is a simple one button, one test manual PAT tester which will test all 240V & 110V portable appliances. There are three earth bond test currents which can be selected on a simple rocker switch, including a 200mA soft test for computers and sensitive I.T. equipment.
The Easypat has a built in lead tester for testing extension leads, IEC leads and adaptors. It will also perform a polarity test and is supplied with the EX332 240V lead test adaptor.

• Tests both 240V and 110V appliances
• Class I, Class II & power lead tests
• Simple one button, one test operation
• Earth bond test currents – 25A, 8A and 200mA for sensitive IT equipment.
• Built in lead tester
£658.80